Installation and troubleshooting of EMFM split electromagnetic flowmeter

Tencent 2017-10-20 16:16:58 Click:
分体式电磁流量计安装和故障排除 Installation and troubleshooting of EMFM split electromagnetic flowmeter
First, the installation attention of split electromagnetic flowmeter

、分体式电磁流量计的传感器应垂直安装,并且流体自下而上流动,以满足固、液两项处于混合的状态。 1. The sensor of the split electromagnetic flowmeter should be installed vertically, and the fluid should flow from the bottom to the top, so that the solid and liquid are mixed. The reason is that solid matter (sand, small stones, etc.) in the medium is prone to
Health precipitation. In addition, there are fish and weeds in the pipeline. Fish swimming in the pipeline will cause the output of the flowmeter to swing back and forth; the swing of the weeds hanging near the electrode will also cause the output of the flowmeter to be unstable. in
A metal filter is installed at the upstream inlet of the flow meter to block fish and weeds from entering the measuring tube.

、分体式电磁流量计防止负压的管路设置操作不当将引起传感器内产生负压。 2. Split-type electromagnetic flowmeter to prevent improper operation of pipeline setting of negative pressure will cause negative pressure in the sensor. When both the upstream and downstream valves of the flowmeter are closed at the same time, if the temperature of the fluid is higher than the air temperature. Shrinking after cooling causes the pressure in the tube to form a negative pressure. The negative pressure caused the liner to peel off from the metal conduit, causing electrode leakage.
、在分体式电磁流量计附近加负压防止阀,打开阀门接通大气压,以防止在传感器内产生负压。 3. Add a negative pressure prevention valve near the split electromagnetic flowmeter and open the valve to connect to atmospheric pressure to prevent negative pressure in the sensor. When a vertical pipeline is connected downstream of the split electromagnetic flowmeter, if the upstream valve of the flow sensor is used to close or adjust the flow, a negative pressure will form in the sensor measurement tube. To prevent negative pressure, add back pressure or use a downstream valve to regulate and close the flow.

、分体式电磁流量计适当的维护空间,大口径流量计往往安装在仪表井内,为了管道安装、接线、检查和维护的方便,需要留有适当的空间。 4. Appropriate maintenance space for the split electromagnetic flowmeter. Large-caliber flowmeters are often installed in instrumentation wells. For the convenience of pipeline installation, wiring, inspection and maintenance, appropriate space needs to be reserved. For the convenience of observation, wiring and maintenance, the instrument should be installed at a certain height from the ground to facilitate cleaning and installation.

Troubleshooting of split electromagnetic flowmeter

Split-type electromagnetic flowmeter may cause inaccurate measurement due to various faults during operation. Generally, the electromagnetic flowmeter's faults during operation can be divided into two categories. One type is the failure caused by the failure of the flowmeter itself and the damage of the components; the other type is the failure caused by the change of external conditions, such as unstable output, numerous flows, and excessive errors.
1 )输出不稳定: ( 1 ) The output is unstable:
、流场不稳; 2 、通过传感器的液体中含有气体、大固体块; 3 、电气连接虚接; 4 、接地不良; 5. 电极渗漏 解决方法: 1. 改造管道、或增加安装假传感器; 2 、正常现象; 3 、检查接线,接好线; 4 、接好地线; 5 、修理传感器。 1. The flow field is unstable; 2. The liquid passing through the sensor contains gas and large solid blocks; 3. The electrical connection is virtual; 4. The grounding is poor; 5. The solution for electrode leakage : 1. Rebuild the pipeline or increase the installation false Sensor; 2. Normal phenomenon; 3. Check the wiring and connect the wire; 4. Connect the ground wire; 5. Repair the sensor.
2 )液体流动无输出: ( 2 ) No output from liquid flow:        
、与转换器之间的信号传输电缆两芯线接反; 2 、电源未接或接触不良; 3. 传感器仪表管道、外壳、端面有渗漏。 1. The two core wires of the signal transmission cable between the converter and the converter are reversely connected; 2. The power supply is not connected or has poor contact; 3. There are leaks in the sensor instrument pipeline, housing, and end surface. 1 、倒线头; 2 、接好电源、保持接触良好; 3 、修理传感器。 Solution: 1. Reverse the cable head; 2. Connect the power supply and keep good contact; 3. Repair the sensor.

3 )液体不流动有输出: ( 3 ) There is output when the liquid is not flowing:

、与转换器之间信号传输电缆连接有断路; 2 、信号电缆到电极连接断路; 3. 电极表面沾污或沉积绝缘层; 4. 接地不良或断路。 1. The signal transmission cable is disconnected from the converter; 2. The signal cable is disconnected from the electrode; 3. The electrode surface is contaminated or the insulation layer is deposited; 4. Poor grounding or open circuit. 1 、接好电缆线; 2 、打开传感器、重新接上; 3 、擦洗电极表面; 4 、接好地线。 Solution: 1. Connect the cable; 2. Turn on the sensor and reconnect it; 3. Scrub the electrode surface; 4. Connect the ground wire.
4 )误差过大: ( 4 ) Excessive error:        
、零点过高; 2 、未完全充满液体; 3 、供电电源畸变过大; 4 、接地不良。 1. Zero is too high; 2. It is not completely filled with liquid; 3. Power supply distortion is too large; 4. Poor grounding.
1. 重新调整零点; 2 、改善管道条件,传感器始终充满液体; 3 、改善供电电源条件,符合正常工作条件; 4 、接好地线。 Solution: 1. Readjust the zero point; 2. Improve the pipeline conditions, the sensor is always filled with liquid; 3 , Improve the power supply conditions to meet normal working conditions;